Weil-McLain · Boiler troubleshooting
Clean cast aluminum heat exchanger, water side
What is going on
Water-side cleaning for the aluminum heat exchanger. Trisodium phosphate (TSP) must not be used because it strips the protective oxide layer.
Check in this order
- Use ONLY Sentinel X400 from WM Technologies. Do not use TSP or other high-pH cleaners.
- Follow the complete startup procedure beginning on page 35 after cleaning.
- After using the cleaning tool on the pin side, spray water downward from above the pins to flush sediment.
- Remove sediment from the bottom of the heat exchanger.
- Disconnect the condensate line at the bottom of the heat exchanger, place a pan under the trap connection, and spray water into the heat exchanger bottom to flush sediment to the condensate outlet.
- Spray water through the condensate line, then reconnect it.
- Reinstall the burner and cover per the access procedure for the model.
Applies to: ALL Ultra Series 4 models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 125. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.