Viessmann · Boiler troubleshooting
Bleed air from the boiler heat exchanger
What is going on
Vent the heat exchanger on the boiler side. Do not use the heating side pressure relief valve for this, as it can damage the equipment.
Check in this order
- Close the field supplied shut-off valves on the heating water side.
- Remove cover panel A.
- Connect the supplied drain hose to heat exchanger air vent valve B and route the other end to the drain.
- Open air vent valve B with the supplied key.
- Fill through sediment faucet C in the heating return and vent using mains pressure until no more air noise is heard.
- Close valve B and fill valve C, then open the heating water shut-off valves.
- Start the venting program from the service menu and end it with OK or the arrow key.
Applies to: Vitodens 222-F B2TB 19, 35, 68, 125
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 222-F B2TB service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.