Viessmann · Boiler troubleshooting

Checking expansion tank and system pressure

Vitocrossal 300 CA3B Dual Fuel

What is going on

Confirm the cold fill pressure matches the diaphragm expansion tank pressure. Carry out on a cold system only.

Likely causes

  • Fill pressure does not match expansion tank pressure
  • Repeated pressure swings indicating a system fault

Check in this order

  1. Drain the system or close the cap valve on the diaphragm expansion tank.
  2. Reduce pressure until the gauge reads 0.
  3. Check that the 60°F (15.5°C) water fill pressure equals the expansion tank pressure.
  4. Follow the expansion tank manufacturer's instructions.
  5. Investigate cyclical pressure swings or large differentials and correct them right away.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.