Checking expansion tank and system pressure
What is going on
Confirm the cold fill pressure matches the diaphragm expansion tank pressure. Carry out on a cold system only.
Likely causes
- Fill pressure does not match expansion tank pressure
- Repeated pressure swings indicating a system fault
Check in this order
- Drain the system or close the cap valve on the diaphragm expansion tank.
- Reduce pressure until the gauge reads 0.
- Check that the 60°F (15.5°C) water fill pressure equals the expansion tank pressure.
- Follow the expansion tank manufacturer's instructions.
- Investigate cyclical pressure swings or large differentials and correct them right away.
Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 75. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.