Clean heat exchanger, flue collar and chimney connection

Vitorond 200 VD2

What is going on

Remove all combustion residue from the heat passages and flue path.

Check in this order

  1. Brush the flue gas passages and the combustion chamber with the supplied cleaning brush.
  2. Use the smaller brush for the tight spaces between the ribs.
  3. Vacuum the combustion residue out.
  4. Clean the chimney connection and flue gas collar through the clean-out openings at the rear of the boiler.

Applies to: All VD2 sizes 320 to 1080

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.