Connect a 24 VAC thermostat through a switching relay
What is going on
A thermostat drives a dry-contact switching relay that feeds the EA1 module. With the contact closed, burner output is load-dependent and the supply water is held at the value in coding address 9b (General group), capped by the electronic supply temperature limit.
Check in this order
- Connect the normally open dry contact of the switching relay (T-T contact) to input DE1, DE2 or DE3 on the EA1 module in the electrical junction box.
- Wire the switching relay to the thermostat and to its power supply per the relay and thermostat instructions (120 VAC supply for the relay).
- In the General group, set coding 3A, 3B or 3C to 2 for the input used.
- If the thermostat is the only room temperature control, set the standard and reduced room temperature set points to 37 ºF (3 ºC) to reduce boiler cycling.
- Keep the contact potential-free; live contacts cause short circuits or phase failure.
Applies to: Vitodens 200-W B2HA 80-100, 285-352
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 installation instructions, p. 52. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.