Viessmann · Boiler troubleshooting

Connect a 24 VAC thermostat through a switching relay

Vitodens 200-W

What is going on

A thermostat drives a dry-contact switching relay that feeds the EA1 module. With the contact closed, burner output is load-dependent and the supply water is held at the value in coding address 9b (General group), capped by the electronic supply temperature limit.

Check in this order

  1. Connect the normally open dry contact of the switching relay (T-T contact) to input DE1, DE2 or DE3 on the EA1 module in the electrical junction box.
  2. Wire the switching relay to the thermostat and to its power supply per the relay and thermostat instructions (120 VAC supply for the relay).
  3. In the General group, set coding 3A, 3B or 3C to 2 for the input used.
  4. If the thermostat is the only room temperature control, set the standard and reduced room temperature set points to 37 ºF (3 ºC) to reduce boiler cycling.
  5. Keep the contact potential-free; live contacts cause short circuits or phase failure.

Applies to: Vitodens 200-W B2HA 80-100, 285-352

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 installation instructions, p. 52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.