ASME high temperature limit installation
What is going on
If the install must meet ASME requirements, an external high limit is needed. Set it at least 20°F above the operating setpoint. The external limit can be set to a maximum of 240°F, and the boiler operating limit is 210°F.
Check in this order
- Install the high limit control in the supply piping between the boiler and its isolation valve.
- Set the external high limit at least 20°F above the operating setpoint.
- Do not set the external high limit above 240°F.
- Confirm the boiler operating limit is 210°F.
- Wire the control as shown on page 46.
Applies to: CGi-25 to CGi-8
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 boiler manual, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.