Weil-McLain · Boiler troubleshooting

ASME high temperature limit installation

CGi Series 5

What is going on

If the install must meet ASME requirements, an external high limit is needed. Set it at least 20°F above the operating setpoint. The external limit can be set to a maximum of 240°F, and the boiler operating limit is 210°F.

Check in this order

  1. Install the high limit control in the supply piping between the boiler and its isolation valve.
  2. Set the external high limit at least 20°F above the operating setpoint.
  3. Do not set the external high limit above 240°F.
  4. Confirm the boiler operating limit is 210°F.
  5. Wire the control as shown on page 46.

Applies to: CGi-25 to CGi-8

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 boiler manual, p. 27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.