Viessmann · Boiler troubleshooting
Choosing the boiler control
What is going on
Pick the control to match the system. Single boiler with weather compensation: Vitotronic 300 GW2/GW2B, or Vitotronic 100 GC1/GC1B with a Vitocontrol panel. Multi-boiler: Vitotronic 100 GC1/GC1B on each boiler with a Vitocontrol-S MW1 / Vitotronic 300-K MW1B cascade unit (up to 4 boilers). Control can be mounted on the left or right side, so state the location at order time. Vitotronic 300 and 300-K need an extension kit for each mixing-valve heating circuit. Refer to the separate control manuals for details.
Check in this order
- Confirm single or multi-boiler layout.
- Confirm the number of mixing-valve heating circuits and whether an extension kit is needed.
- Specify control mounting side at order time.
- Check LON requirements if building management integration is needed.
Applies to: Vitorond 200 VD2A
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2A Technical Data Manual, p. 17-18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.