Field wiring rules for the boiler and controls
What is going on
Wiring must follow the National Electrical Code (or CSA C22.1 in Canada) and local codes. Use Class 1 wiring, and sheath field-supplied 120 VAC wiring in flexible metal conduit.
Check in this order
- Use 14 ga. or heavier wire for supply and control wiring.
- If replacing original boiler wire, use 105 C wire or equivalent.
- Provide electrical ground at the boiler as required by codes.
- Provide a disconnect, overload protection and low water cut-off as required by local codes.
- Connect incoming line voltage hot to L1 and neutral to L2 on the Hydrostat 3250-Plus.
- Turn off the power, including the boiler service switch, before any wiring work.
Applies to: Hydrostat 3250-Plus control with Carlin or Beckett or Riello burners
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 VR1 installation and service manual, p. 29 and p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.