Convert from natural gas to liquid propane gas

Vitodens 200-W B2HA

What is going on

The boiler is factory set for natural gas. Coding address 82 is 0 for natural gas. Coding 11 must be set to 9 before 82 can be changed.

Check in this order

  1. Set gas valve adjusting screw A to 2 with a 2.5 mm hex key.
  2. Switch the ON/OFF switch 8 to ON. Slide the black control cover out to reach it.
  3. Enter coding level 2 (see page 47).
  4. Open the General group.
  5. Set coding address 11 to 9.
  6. Set coding address 82 to 1 (liquid propane gas).
  7. Return to coding address 11 and select any value except 9.
  8. Exit coding level 2 and open the gas shut-off valve.
  9. Apply the supplied fuel conversion labels.

Applies to: Vitodens 200-W B2HA 19, 28, 35

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.