Navien · Boiler troubleshooting

Installing the DHW pressure relief valve

NCB700

What is going on

A DHW pressure relief valve must be fitted by a licensed professional. It is not supplied with the boiler and is required. Approved examples listed: Wilkins P-1000A (Zurn), Conbraco 17-402-04, Watts 3L (M7), Cash Acme FWL-2 3/4 in. Its discharge capacity must be at least the DHW system's maximum pressure rating, and its BTU/H rating must be at least the boiler's maximum input.

Check in this order

  1. Confirm the valve's discharge capacity meets or exceeds the DHW maximum pressure rating.
  2. Confirm the valve's BTU/H rating meets or exceeds the boiler's maximum input BTU/H.
  3. Install the valve as close to the boiler as possible. No other valve may sit between the relief valve and the boiler.
  4. Run the discharge line to within 2 to 6 in (50-150 mm) of the floor or a floor drain.
  5. Keep the discharge line free-draining with no reducing coupling or restriction.
  6. Route discharge so hot water cannot splash people or nearby equipment.
  7. Do not plug the valve. If it discharges periodically, check for thermal expansion in the closed supply and contact the water supplier or plumber.

Applies to: NCB700 DHW pressure relief valve

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.