Navien · Boiler troubleshooting
Installing the DHW pressure relief valve
What is going on
A DHW pressure relief valve must be fitted by a licensed professional. It is not supplied with the boiler and is required. Approved examples listed: Wilkins P-1000A (Zurn), Conbraco 17-402-04, Watts 3L (M7), Cash Acme FWL-2 3/4 in. Its discharge capacity must be at least the DHW system's maximum pressure rating, and its BTU/H rating must be at least the boiler's maximum input.
Check in this order
- Confirm the valve's discharge capacity meets or exceeds the DHW maximum pressure rating.
- Confirm the valve's BTU/H rating meets or exceeds the boiler's maximum input BTU/H.
- Install the valve as close to the boiler as possible. No other valve may sit between the relief valve and the boiler.
- Run the discharge line to within 2 to 6 in (50-150 mm) of the floor or a floor drain.
- Keep the discharge line free-draining with no reducing coupling or restriction.
- Route discharge so hot water cannot splash people or nearby equipment.
- Do not plug the valve. If it discharges periodically, check for thermal expansion in the closed supply and contact the water supplier or plumber.
Applies to: NCB700 DHW pressure relief valve
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.