Viessmann · Boiler troubleshooting
Hydrostatic pressure test before connecting power and piping
What is going on
Leak test the boiler water side before it is connected to piping or electrical supply.
Check in this order
- Install the safety devices first, then put a temporary cap on the ¾ in. x 2 in. nipple.
- Cap the supply and return connections.
- Connect a ½ in. garden hose to the boiler fill valve at the bottom of the boiler and fill slowly to the test pressure shown on the pressure gauge.
- Hold the pressure for 15 minutes and do not leave the boiler unattended.
- Check all joints and safety devices with a flashlight for leaks. A lower gauge reading usually means water loss. Repair all leaks.
- After 15 minutes, open the drain valve slowly to release pressure. Remove the caps and install the pressure relief valve in place of the ¾ in. cap.
- Continue installation only after the boiler passes the test.
Applies to: Vitodens 200-W B2HA 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 installation instructions, p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.