Insufficient hot water quantity
What is going on
Low DHW flow on a Rinnai E50CRN, E75CRN, E75CRP, E110CRN or E110CRP boiler. Hot water comes out, but not enough of it. Usually an install detail or scale, so the checks below go in that order.
Likely causes
- Hot and cold connections swapped, because the unit is plumbed left hot, right cold
- Wrong or dirty flow reducing valve restricting the flow
- Scale in the plate heat exchanger, common with hard water
Check in this order
- Check connections left is hot, right is cold, since a swap throttles output
- Check the restrictor type and cleanliness; clean or replace it, because a clogged or wrong one cuts flow directly
- Descale or replace the plate heat exchanger if nothing else helps, because scale narrows the passages
- Compare flow at several taps to see whether it is the boiler or the building piping
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.77 (15.4). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.