What is going on

Check supply pressure at the gas combination valve inlet port A before and during operation.

Check in this order

  1. Remove the boiler enclosure panel as shown on p. 11.
  2. Close the field-supplied gas shutoff valve.
  3. Loosen the screw at inlet gas pressure port A on the gas combination valve, do not remove it fully, and connect a manometer.
  4. Open the gas shutoff valve.
  5. Measure static pressure. Maximum is 14 in. w.c. for NG and 14 in. w.c. for LPG.
  6. Record the static reading in the Maintenance Record (p. 113).
  7. Start the boiler with the ON/OFF switch "8" (flip up the lower orange cover).
  8. Measure running pressure using a gauge resolving at least 0.04 in. w.c.
  9. Record the gas type and running pressure in the Maintenance Record (p. 113).
  10. Switch the boiler off, close the gas shutoff valve, remove the manometer and retighten the screw at port A.

Applies to: Vitocrossal 300 CU3A gas supply

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.