Measure static and running gas pressure
What is going on
Check supply pressure at the gas combination valve inlet port A before and during operation.
Check in this order
- Remove the boiler enclosure panel as shown on p. 11.
- Close the field-supplied gas shutoff valve.
- Loosen the screw at inlet gas pressure port A on the gas combination valve, do not remove it fully, and connect a manometer.
- Open the gas shutoff valve.
- Measure static pressure. Maximum is 14 in. w.c. for NG and 14 in. w.c. for LPG.
- Record the static reading in the Maintenance Record (p. 113).
- Start the boiler with the ON/OFF switch "8" (flip up the lower orange cover).
- Measure running pressure using a gauge resolving at least 0.04 in. w.c.
- Record the gas type and running pressure in the Maintenance Record (p. 113).
- Switch the boiler off, close the gas shutoff valve, remove the manometer and retighten the screw at port A.
Applies to: Vitocrossal 300 CU3A gas supply
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.