Navien · Boiler troubleshooting

Space heating water piping and pressure relief valve

NFB

What is going on

A pressure relief valve must be installed on the space heating supply. Use threaded connections only.

Check in this order

  1. Install the included 3/4 in, 50 psi maximum pressure relief valve on the space heating supply.
  2. Use the ASME-approved space heating relief valve supplied, or install on the Navien manifold or top connection with the air vent.
  3. Do not solder pipe directly onto the water connections.
  4. Flush the whole system of sediment, flux, scale and debris before connecting the boiler.
  5. Fit the PRV-air vent adapter and clip on the top connection, then install the air vent bushing and air vent.
  6. Remove the air vent cap before filling, and replace it when the system is full.
  7. Make sure the vent cap is fitted and all pump vent screws are tight before testing.

Applies to: NFB-301C/399C

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NFB-C quick installation guide, p. 2. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.