Installing boiler safety devices

Vitodens 222-F

What is going on

Fit the pressure relief valve, drain valve and isolation valve, then pipe the relief discharge to a floor drain.

Check in this order

  1. Remove the pressure relief valve, drain valve and fittings from the box.
  2. Apply enough pipe sealant to both ends of all fittings and install them onto the tees.
  3. Install the pressure relief valve and isolation valve and tighten them.
  4. Run the relief discharge pipe to a floor drain with an unthreaded end, ending about 6 in. (150 mm) above the drain.
  5. Check there is no shutoff valve in the discharge pipe and the pipe diameter is not reduced.

Applies to: Vitodens 222-F, B2TB safety devices

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F, B2TB installation instructions, p. 28-29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.