Checking on-site gas connections for leaks
What is going on
Check the on-site gas connections and the gas valve sealing points for leakage at the gauge connections. Do not use leak detection spray near electrical contacts, and do not use it in a way that could affect operation.
Check in this order
- Install new gaskets at all detached on-site connections.
- Open the gas shut-off valve.
- Check the sealing points at the input side of the combination gas valve for leakage.
- Start the boiler (see the commissioning sequence).
- Check the output side of the combination gas valve, the seal between fan and burner plate, and the seal between fan and Venturi tube for leakage.
- Check the gas gauge connections for leakage.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.