Beckett · Boiler troubleshooting

NX burner: start-up settings on Ultra Oil boilers

Beckett NX

What is going on

Nozzle, pump pressure and head/air starting points for each Ultra Oil size. The NX is shipped set for 1.00 GPH on the UO-3.

Likely causes

  • Wrong nozzle or pressure for the boiler size
  • UO-3 changed to 0.80 GPH without the other changes

Check in this order

  1. UO-3 CV (spec WL6403) and UO-3 DV (WL6503), air tube NX70LC, 1-3/4 in. insertion.
  2. UO-3 at 0.80 GPH: nozzle 0.65 x 60 A (Delavan) or 0.65 x 60 B (Hago), 150 psig, head/air 3.50 (CV) or 3.25 (DV).
  3. UO-3 at 1.00 GPH: nozzle 0.75 x 60 B (Hago or Delavan), 175 psig, head/air 4.00 (CV) or 3.75 (DV).
  4. UO-4 CV (WL6404) and DV (WL6504), 1.20 GPH, air tube NX90LD, 3-1/2 in. insertion: nozzle 1.00 x 60 W (Delavan) or 1.00 x 60 AB (Danfoss), 140 psig, head/air 2.50.
  5. UO-5 CV (WL6405) and DV (WL6505), 1.40 GPH, NX90LD, 3-1/2 in.: nozzle 1.10 x 70 B (Hago or Delavan), 160 psig, head/air 2.50.
  6. Going to 0.80 GPH on a UO-3: change the nozzle, set pump pressure and head/air from the list, and lay the 14 x 16 in. blanket on the combustion chamber floor.
  7. All direct vent (DV) boilers need the combustion chamber blanket (comes with the burner).
  8. Pump pressure is above 100 psig, so the real firing rate is higher than the number stamped on the nozzle (1.00 GPH at 140 psig is about 1.18 GPH).
  9. Head/air numbers are starting points only. Final setting with an analyzer.
  10. Check the burner spec number on the carton against this list before firing. Nozzle columns in the text export were split across lines: confirm against Table 1 p.4-5.

Applies to: Beckett NX burners on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Table 1 Burner Configurations p.4-5; nozzle flow note p.18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.