Beckett · Boiler troubleshooting
NX burner: start-up settings on Ultra Oil boilers
What is going on
Nozzle, pump pressure and head/air starting points for each Ultra Oil size. The NX is shipped set for 1.00 GPH on the UO-3.
Likely causes
- Wrong nozzle or pressure for the boiler size
- UO-3 changed to 0.80 GPH without the other changes
Check in this order
- UO-3 CV (spec WL6403) and UO-3 DV (WL6503), air tube NX70LC, 1-3/4 in. insertion.
- UO-3 at 0.80 GPH: nozzle 0.65 x 60 A (Delavan) or 0.65 x 60 B (Hago), 150 psig, head/air 3.50 (CV) or 3.25 (DV).
- UO-3 at 1.00 GPH: nozzle 0.75 x 60 B (Hago or Delavan), 175 psig, head/air 4.00 (CV) or 3.75 (DV).
- UO-4 CV (WL6404) and DV (WL6504), 1.20 GPH, air tube NX90LD, 3-1/2 in. insertion: nozzle 1.00 x 60 W (Delavan) or 1.00 x 60 AB (Danfoss), 140 psig, head/air 2.50.
- UO-5 CV (WL6405) and DV (WL6505), 1.40 GPH, NX90LD, 3-1/2 in.: nozzle 1.10 x 70 B (Hago or Delavan), 160 psig, head/air 2.50.
- Going to 0.80 GPH on a UO-3: change the nozzle, set pump pressure and head/air from the list, and lay the 14 x 16 in. blanket on the combustion chamber floor.
- All direct vent (DV) boilers need the combustion chamber blanket (comes with the burner).
- Pump pressure is above 100 psig, so the real firing rate is higher than the number stamped on the nozzle (1.00 GPH at 140 psig is about 1.18 GPH).
- Head/air numbers are starting points only. Final setting with an analyzer.
- Check the burner spec number on the carton against this list before firing. Nozzle columns in the text export were split across lines: confirm against Table 1 p.4-5.
Applies to: Beckett NX burners on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Table 1 Burner Configurations p.4-5; nozzle flow note p.18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.