Check flame and combustion at high and low fire
What is going on
Combustion is checked with calibrated instruments at high fire and low fire, with the firing rate forced in Manual test mode.
Check in this order
- Call for heat from one heat demand input.
- Press and hold the UP and DOWN arrow keys for five seconds to open the installer menus.
- Go to DIAGNOSTICS and then Manual test mode, and force the firing rate to High.
- Check that the high fire flame is blue and stable and the burner surface has orange dots.
- Pull the flue temperature sensor and insert a calibrated combustion test probe.
- Measure CO2 (or O2) and CO. CO2 must be within 1.0% of the Figure 73 values.
- Set the firing rate to Low and repeat the flame check and combustion test.
- Set the firing rate back to AUTO.
- Reinstall the flue gas temperature sensor before leaving the boiler.
Applies to: SlimFit SF-550 and SF-750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 boiler manual, p. 86. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.