Weil-McLain · Boiler troubleshooting
Initial checks before diagnosing a boiler problem
What is going on
Check these items first when servicing the boiler. Always turn off power before servicing. The boiler ON/OFF switch does not remove all power from internal wiring.
Check in this order
- Check for 120 Vac to the boiler (acceptable range 102 Vac to 132 Vac).
- Confirm the thermostat is calling for heat and the contacts are closed; check for 24 Vac between the thermostat wire nuts and ground.
- Confirm all external limit controls are installed and closed, or have temporary jumpers for testing.
- Confirm connectors are fully plugged in at the module and the originating control.
- Check gas pressures against the Gas Piping section (page 62).
- Label all wires before disconnecting. Never jumper a device except for momentary testing.
Applies to: SVF 500/600 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 boiler manual, p. 119. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.