Boiler short-cycling or inadequate DHW supply

Vitodens 100-W B1HE/B1KE

What is going on

Likely caused by DHW piping that is too small or by a DHW coil whose pressure drop is too high for the boiler pump head.

Likely causes

  • DHW supply or return piping between boiler and tank is smaller than the minimum stated in the manual.
  • Non-Viessmann DHW tank coil pressure drop is higher than the boiler pump head can overcome.

Check in this order

  1. Check DHW supply and return pipe size against the minimum on page 21 (the size is garbled in this extract; confirm it in the full manual).
  2. For non-Viessmann tanks, calculate DHW coil pressure drop against boiler pump head.
  3. Correct piping or tank selection so the boiler heat exchanger gets sufficient flow.

Applies to: Vitodens 100-W B1HE with DHW storage tank, B1KE

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W B1HE/B1KE technical data manual, p. 21 and p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.