Viessmann · Boiler troubleshooting

Match control unit to modulating burner

Vitotronic 100

What is going on

Measures burner output at the set points and enters the values into coding. The burner must already be adjusted. Set the minimum output as low as possible, taking the chimney/flue system into account.

Check in this order

  1. Start up the burner.
  2. Press 9 and OK together for about 2 seconds.
  3. Use the up button to activate 'Modulating burner open' (display 2). Wait until the actuator is at maximum output.
  4. Record the maximum burner output from fuel consumption.
  5. Activate 'Modulating burner closed' (display 4) and time how long the actuator takes to reach minimum output.
  6. Record the minimum (basic) output from fuel consumption.
  7. Activate 'Modulating burner open' (display 2). After one-third of the time from step 5, activate 'Modulating burner neutral' (display 3).
  8. Record the partial output from fuel consumption.
  9. Press OK to end the relay test.
  10. Enter the recorded values into coding level 1 (see the modulating burner coding table).

Applies to: Modulating burner start-up

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 90-91. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.