Viessmann · Boiler troubleshooting

Burner connection and burner control wiring (CM2, plug-in burner)

Vitotronic 300 GW2

What is going on

For burners with plug-in connection. Burner cables come with the Vitotronic. Connect the burner per local codes. Terminal 1 is the phase from the fixed high limit, terminal 2 is modulating down, and terminal 3 is modulating up or 2nd stage ON. Terminal S3 takes the burner fault signal and B4 takes the burner hours counter. T1 and T2 are the control circuit. Colour codes: BK black, BN brown, BU blue.

Check in this order

  1. Disconnect power to the burner and the boiler control.
  2. Connect the 7-pole burner plug to the matching counter plug on the boiler control unit.
  3. Connect the 3-pole burner plug to the matching counter plug on the boiler control unit.
  4. Connect the 7-pole plug and the 3-pole plug to the burner.

Applies to: Vitotronic 300 GW2 with CM2 control, plug-in burner connection

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.