Viessmann · Boiler troubleshooting
Pressure relief valve piping
What is going on
Mount the pressure relief valve on the top of the boiler or on the boiler safety supply. Do not install valves, shut-offs or obstructions between the boiler and the relief valve or on its discharge. The discharge must be the same size as the outlet, run horizontally over the side of the boiler and then down to about 1 ft. (300 mm) above the floor, as close to a floor drain as possible. Do not pipe it outdoors or to any area that can freeze.
Check in this order
- Mount the relief valve on the top of the boiler or its safety supply.
- Keep the outlet clear of any valve or obstruction.
- Pipe the discharge the same size as the outlet, horizontally then vertically down to about 1 ft. (300 mm) above the floor.
- Run the discharge close to a floor drain and secure it with hangers or brackets.
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 44. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.