Viessmann · Boiler troubleshooting
Monthly owner/operator checks
What is going on
Routine checks the owner or operator should do each month. Record any deficiency for the heating technician.
Check in this order
- Check the system pressure frequently.
- Confirm the boiler control operates correctly per the control instructions.
- Inspect all seals and retighten or replace as needed.
- Confirm combustion air and ventilation air into and out of the mechanical room is maintained at all times.
- Confirm nothing blocks combustion and ventilation air and no chemicals, garbage, gasoline, combustibles or flammable liquids or vapours are stored near the boiler.
- Look for water on the floor from the relief valve discharge, any pipe, joint, valve or air vent.
- Test the pressure relief valve and confirm it operates properly per the valve instructions.
- Check that all operational high limits work properly.
- If a condensate neutralization system is fitted, check it works, check the media condition and fill level, and check flue gas condensate pH (minimum 6.5).
- Check external vent pipe joints for moisture and check for ice on the vent pipe or chimney outlet in winter.
Applies to: Vitocrossal 200 CI2, all sizes
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 98. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.