Weil-McLain · Boiler troubleshooting

Check blower speeds in manual test mode

ECO Tec Series 3

What is going on

Confirm blower rpm at low, ignition and high fire against the firing rate tables.

Check in this order

  1. Set the correct altitude in the boiler setup menu first.
  2. Go to DIAGNOSTICS, then Manual test mode.
  3. Set the firing rate to LOW and record the blower rpm. It should be within 50 rpm of the Figure 125 (NG) or 126 (LP) value, unless low fire was raised for priority need.
  4. Set the firing rate to IGNITION and record rpm. It should be within 50 rpm of the Figure 125 or 126 value.
  5. Set the firing rate to HIGH and record rpm. It should be within 50 rpm of the Figure 125 (NG), 126 (LP) or 127 (199 NG/LP) value.
  6. If any value is outside range, contact the factory.
  7. Changing min or max blower speeds affects AFUE ratings.

Applies to: ECO Tec Series 3 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 142-143. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.