Weil-McLain · Boiler troubleshooting
Set up proof of closure for a flow switch or combustion air damper
What is going on
Proof of closure must be wired with isolated contacts. The P7 circuit carries 5 VDC. The blower will not start until the switch is closed.
Likely causes
- Proof of closure open after the 4-minute window
- Proof of closure opens during firing
Check in this order
- Clip only the purple wire on P7 pin 3 to make room for the field wiring. Do not clip any other P7 wire.
- Strip the jumper ends and wire the devices as shown in Figure 52.
- Connect the right side of each jumper only to the right side of other jumpers.
- For a combustion air damper, set Input 3 as AUX PUMP/OUTPUT.
- Set the AUX PUMP/OUTPUT operating mode to ANY BURNER DEMAND.
- Connect Output 3 (120 VAC) to the damper motor. Use an isolation relay if the damper needs another voltage or more than 2.2 A.
- A flow switch needs no control settings.
- Expect 4 minutes for the switch to close after a call. If it stays open, or opens during firing, the control locks out and clears when the switch closes again.
Applies to: SlimFit 550/750 Series 3 boiler
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual, p. 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.