Set up proof of closure for a flow switch or combustion air damper

SlimFit Series 3

What is going on

Proof of closure must be wired with isolated contacts. The P7 circuit carries 5 VDC. The blower will not start until the switch is closed.

Likely causes

  • Proof of closure open after the 4-minute window
  • Proof of closure opens during firing

Check in this order

  1. Clip only the purple wire on P7 pin 3 to make room for the field wiring. Do not clip any other P7 wire.
  2. Strip the jumper ends and wire the devices as shown in Figure 52.
  3. Connect the right side of each jumper only to the right side of other jumpers.
  4. For a combustion air damper, set Input 3 as AUX PUMP/OUTPUT.
  5. Set the AUX PUMP/OUTPUT operating mode to ANY BURNER DEMAND.
  6. Connect Output 3 (120 VAC) to the damper motor. Use an isolation relay if the damper needs another voltage or more than 2.2 A.
  7. A flow switch needs no control settings.
  8. Expect 4 minutes for the switch to close after a call. If it stays open, or opens during firing, the control locks out and clears when the switch closes again.

Applies to: SlimFit 550/750 Series 3 boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual, p. 55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.