Viessmann · Boiler troubleshooting
Check boiler, DHW tank, flow and low-loss header temperature sensors
What is going on
Sensor type is NTC 10 kΩ. Compare measured resistance with the curve (curve not reproduced in this extract). Drain the boiler before replacing the boiler water sensor.
Check in this order
- Boiler temperature sensor remove the lead to the boiler water temperature sensor (§ or §A) and measure resistance.
- DHW tank sensor pull plug % from the cable harness at the control unit and measure resistance.
- Supply or low-loss header sensor pull plug X3 from the control unit and measure across terminals X3.4 and X3.5. Only one of these sensors may be used.
- Replace the sensor if the values deviate severely from the curve.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB service instructions, p. 84. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.