Weil-McLain · Boiler troubleshooting
Reinstall cover plate, blower, burner and igniter
What is going on
Reassembly after cleaning. Use a torque wrench and follow the torque values in the torque setting.
Likely causes
- Improperly seated gaskets
- Over-torqued fasteners
Check in this order
- Place the cover plate on the heat exchanger with the blower flange facing front and square
- Install all bolts finger-tight from the heat exchanger to the cover plate
- Tighten all bolts in a star pattern with a 5 mm Allen wrench to the torque in the torque setting
- Place the blower, venturi and gas valve assembly into the boiler; attach the blower to the cover plate and install the four nuts finger-tight, then torque them
- Reinstall the flex gas line to the inlet pipe with two pipe wrenches
- Reconnect the blower harnesses
- Insert a new burner gasket into the cover plate, set the burner in place and torque the six bolts in a star pattern
- Insert the burner access hatch seal and access cover; torque the five bolts
- Insert the ignition electrode with gasket; hand-tighten the two screws, then torque them
- Reattach the igniter cable and ground wire
- Reinstall the condensate trap to the heat exchanger drain and tighten the hose clamp
- Check the seal of the ignition electrode, igniter gasket and cover plate so they are gas-tight to prevent gas leaks or CO emissions
Applies to: SVF 500/600 Series 1 boiler
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 boiler manual, p. 112. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.