Field test of fixed high limit, simulation 1 (CSD-1)
What is going on
Checks the fixed high limit by overheating the boiler with the flow blocked. Only where required by law. Viessmann is not responsible for damage caused by overheating during this test.
Check in this order
- Close the boiler valve and jumper across the flow switch.
- Run the boiler at high fire. On B2TB models, set coding address 06 to maximum so the coding card shuts the burner down.
- Let the boiler temperature keep rising until the fixed high limit trips.
- Once the fixed high limit has tripped, slowly open the boiler valve to cool the boiler down.
- Reset the boiler control manually, since a tripped fixed high limit requires manual reset.
Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F, B2TB installation instructions, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.