Check combustion quality

Vitodens 222-F

What is going on

Measure the CO2 or O2 content of the flue gas, then use the air factor table to find the air factor. The result should fall within λ 1.24 to 1.44.

Check in this order

  1. Measure CO2 or O2 in the flue gas.
  2. Find the matching air factor λ in the air factor table for your gas type (natural gas or liquid propane).
  3. Confirm λ is between 1.24 and 1.44.

Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 222-F B2TB service instructions, p. 34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.