Boiler fires or pumps run with no call for heat

Weil-McLain ECO Tec Series 3

What is going on

Two built-in functions can do this. Freeze protection starts the chosen circulators when the heat exchanger sensors drop below 45°F, fires the burner at low fire below 40°F, and stops both above 48°F. Circulator exercising runs each selected pump for 10 seconds after 72 hours with no run time.

Likely causes

  • Freeze protection active
  • Circulator exercising

Check in this order

  1. Check boiler water temperature on the information screen. Low readings near 40-48°F point to freeze protection.
  2. Look at contractor menu > Pump Settings > Freeze Protect Circs and Circulator Exercising to see which pumps are set.
  3. A 10-second pump run after a long idle period is the exercise function, not a fault.

Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Pump Settings, p.59. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.