Gas piping leak test and purge
What is going on
Test the gas supply piping for leaks and purge air before first firing. Never use an open flame to find leaks.
Check in this order
- Connect and size the gas supply piping to local and national codes.
- Perform the leak test with an approved liquid bubble solution only.
- Keep the spray off electrical parts, wires and connectors, and off the gas valve regulator and its vent opening.
- Isolate the boiler from the piping with its manual shut-off valve for tests at 14 in. w.c. (3.5 kPa) or less.
- Disconnect the boiler and its shut-off valve for tests above 14 in. w.c. (3.5 kPa).
- Purge air from the gas line with an approved purge burner or vent to outdoors.
- Have a licensed gas fitter complete the leak test during the initial trial burner run, since unions and the gas manifold are not factory tested.
Applies to: Vitorond 200 VD2A gas installations
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2A installation manual, p. 35. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.