Viessmann · Boiler troubleshooting
Burner reassembly and CO2 check after cleaning
What is going on
Tighten fasteners to specified torque and check gas tightness before starting. Leak detection spray can cause faulty operation.
Check in this order
- Position the burner plate with burner mesh on the 8 studs and tighten nuts to 7.3 lb.ft (10 Nm).
- Place the upper burner section on the burner plate and tighten M10 nuts to 7.3 lb.ft (10 Nm).
- Push on the ignition and ionization electrode connectors.
- Insert connectors at the plug-in panel and burner control unit; connect the mains plug last.
- Fit the gas connection pipe and check the fitting for gas tightness.
- Keep leak detection spray away from electrical contacts.
- Start the burner and run a function test.
- Measure CO2 after each burner dismantling per pages 66 and 67, and record it in the maintenance record on page 158.
Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 74. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.