Viessmann · Boiler troubleshooting

Wiring pumps that draw more than 2 FLA

Vitocrossal 300 CA3B Dual Fuel

What is going on

Pumps drawing over 2 FLA on 120V, 240V or 208/460/575V 3-phase circuits should not be run straight from the control. Switch them through a field-supplied contactor.

Check in this order

  1. Use a field-supplied contactor or relay with a 120VAC, 1A coil.
  2. Mount the contactor on the DIN rail in the junction box.
  3. Feed the pump from the power supply with disconnect and protection through the contactor.
  4. Wire the contactor coil from the control output.
  5. Pumps under 2 FLA connect directly to the DIN rail in the junction box.

Applies to: 120V, 240V and 208/460/575V 3-phase pumps

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 25-26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.