Viessmann · Boiler troubleshooting
Wiring pumps that draw more than 2 FLA
What is going on
Pumps drawing over 2 FLA on 120V, 240V or 208/460/575V 3-phase circuits should not be run straight from the control. Switch them through a field-supplied contactor.
Check in this order
- Use a field-supplied contactor or relay with a 120VAC, 1A coil.
- Mount the contactor on the DIN rail in the junction box.
- Feed the pump from the power supply with disconnect and protection through the contactor.
- Wire the contactor coil from the control output.
- Pumps under 2 FLA connect directly to the DIN rail in the junction box.
Applies to: 120V, 240V and 208/460/575V 3-phase pumps
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel installation instructions, p. 25-26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.