Check vent system operation with candle or match test
What is going on
Check the vent system at least once a month during the heating season. A flame held at the draft hood should burn undisturbed when the vent is working.
Likely causes
- Obstructions in the vent system
- Exhaust fans in the boiler room causing improper venting
Check in this order
- Check the vent system at least once a month during the heating season.
- With the boiler firing, hold a candle or match below the lower edge of the draft hood skirt.
- If the flame burns undisturbed, the vent is working properly.
- If the flame blows out or flickers strongly, inspect for obstructions or other causes such as exhaust fans in the boiler room.
Applies to: EG / PEG boilers with draft hood
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 boiler manual, p. 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.