Viessmann · Boiler troubleshooting

Wire circulation and heating pumps

Vitotronic 300

What is going on

Wiring depends on pump voltage. Pump outputs differ between VD2/VD2A/CT3 and CM2 controls; see the pump terminal table.

Check in this order

  1. Install pumps per the pump manufacturer's instructions.
  2. For 120 VAC pumps total pump load must not exceed 4 A; each output rated max 2 FLA; use AWG 14 cable; connect the 3-wire pump cable to the matching terminals.
  3. For larger 120 VAC pumps, use a contactor.
  4. For 240 VAC or 3-phase pumps power the pump through a contactor and/or motor starter, not directly from the control.
  5. Select the contactor and connecting wire to suit the pump rating (max 2 FLA coil rating, AWG 14).
  6. Connect pump and supply to the contactor, then connect the contactor coil to the matching terminals.
  7. Follow local and national codes for all connections and wire sizes.

Applies to: Vitotronic 300 GW2 pump outputs

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 Installation and Service Instructions, p. 30-31. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.