Wire circulation and heating pumps
What is going on
Wiring depends on pump voltage. Pump outputs differ between VD2/VD2A/CT3 and CM2 controls; see the pump terminal table.
Check in this order
- Install pumps per the pump manufacturer's instructions.
- For 120 VAC pumps total pump load must not exceed 4 A; each output rated max 2 FLA; use AWG 14 cable; connect the 3-wire pump cable to the matching terminals.
- For larger 120 VAC pumps, use a contactor.
- For 240 VAC or 3-phase pumps power the pump through a contactor and/or motor starter, not directly from the control.
- Select the contactor and connecting wire to suit the pump rating (max 2 FLA coil rating, AWG 14).
- Connect pump and supply to the contactor, then connect the contactor coil to the matching terminals.
- Follow local and national codes for all connections and wire sizes.
Applies to: Vitotronic 300 GW2 pump outputs
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 Installation and Service Instructions, p. 30-31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.