Weil-McLain · Boiler troubleshooting
Annual startup: inspect boiler area, interior and door gaskets
What is going on
Confirm the area and the interior are clear before the burner work.
Check in this order
- Address any problems the owner reported and fix them before going on.
- Confirm the boiler area has no combustibles, gasoline or flammable vapors and liquids.
- Confirm the air intake area has none of the contaminants listed on page 22. If any are present, remove them. If they cannot be removed, reinstall the air and vent lines per the manual and the SlimFit Boiler Vent Supplement.
- Remove the front door and inspect the boiler interior.
- Inspect all door gaskets. Replace any that are damaged.
- Remove the venturi air inlet silencer, clean it if needed, and reinstall it.
- Vacuum sediment from inside the boiler and its components. Remove any obstructions.
- Do not use solvents on any boiler component.
Applies to: SlimFit 550 and 750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 92. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.