Viessmann · Boiler troubleshooting
Connect external shut-off (aBÖ) and emergency operation
What is going on
A dry contact at terminals 16 and 17 gives a controlled switch-off when opened. Use it for safety switch-off only, for example through a limit thermostat. With the contact open, the system has no frost protection and the boiler is not held at minimum water temperature.
Check in this order
- Disconnect power before working on the wiring.
- Remove the jumper between terminals 16 and 17.
- Connect a dry contact to the terminals.
- For emergency operation, move the jumper from terminals 16 and 17 to terminals 17 and 18.
- See the controlled switch-off pages (52 to 59) for details.
Applies to: VD2, VD2A and CT3 controls
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 installation and service instructions, p. 75. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.