Viessmann · Boiler troubleshooting

Connect external shut-off (aBÖ) and emergency operation

Vitotronic 100

What is going on

A dry contact at terminals 16 and 17 gives a controlled switch-off when opened. Use it for safety switch-off only, for example through a limit thermostat. With the contact open, the system has no frost protection and the boiler is not held at minimum water temperature.

Check in this order

  1. Disconnect power before working on the wiring.
  2. Remove the jumper between terminals 16 and 17.
  3. Connect a dry contact to the terminals.
  4. For emergency operation, move the jumper from terminals 16 and 17 to terminals 17 and 18.
  5. See the controlled switch-off pages (52 to 59) for details.

Applies to: VD2, VD2A and CT3 controls

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 installation and service instructions, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.