Viessmann · Boiler troubleshooting

Heating water connections

Vitodens 100-W WB1B

What is going on

Flush the system before connecting the boiler, then connect water lines. Do not exceed the maximum operating or test pressure.

Check in this order

  1. Flush the heating system thoroughly, especially if connecting to an existing system.
  2. Connect the boiler water supply and return (3/4 in each), plus drain and fill as needed.
  3. Install isolation valves so components can be isolated.
  4. Meet all local plumbing codes.
  5. Keep operating pressure at or below 3 bar (45 psig).
  6. Keep test pressure at or below 4 bar (60 psig).

Applies to: Boiler water piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 100-W WB1B installation manual, p. 20. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.