Set up a Vitodens 200 / B2HA cascade with the Vitotronic 300-K MW2C

Versatronik 581 / 581D

What is going on

The cascade control must be addressed as LON 9 so the boilers can use LON addresses 1 through 8. KMK communication is possible but gives less information.

Check in this order

  1. Set the MW2C LON address 77 to a value of 9.
  2. Set the boilers from LON address 1 through 8 (coding address 77).
  3. Set the gateway configuration nviCasConfig to 1 (cascade at LON address 9).
  4. If the boilers communicate by KMK instead of LON, set nviCommConfig to 1.
  5. Expect less data when KMK is used than when LON is used.

Applies to: Vitotronic 300-K MW2C for Vitodens 200 / B2HA

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 581 LON gateway manual, p. 13-14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.