Set up a Vitodens 200 / B2HA cascade with the Vitotronic 300-K MW2C
What is going on
The cascade control must be addressed as LON 9 so the boilers can use LON addresses 1 through 8. KMK communication is possible but gives less information.
Check in this order
- Set the MW2C LON address 77 to a value of 9.
- Set the boilers from LON address 1 through 8 (coding address 77).
- Set the gateway configuration nviCasConfig to 1 (cascade at LON address 9).
- If the boilers communicate by KMK instead of LON, set nviCommConfig to 1.
- Expect less data when KMK is used than when LON is used.
Applies to: Vitotronic 300-K MW2C for Vitodens 200 / B2HA
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 581 LON gateway manual, p. 13-14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.