Viessmann · Boiler troubleshooting

Set up LON communication between control units

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Steps to set system type, boiler number and LON participant numbers. The LON communication module must be plugged in first.

Check in this order

  1. Vitotronic 100 set coding 1, address 01 to 2 (multi-boiler system).
  2. Vitotronic 100 set the boiler number in coding 1, address 07.
  3. Vitotronic 100 set the LON participant number in coding 1, address 77. Each LON participant number can only be used once.
  4. Vitocontrol-S set the number of boilers in coding 1, address 35.
  5. Vitocontrol-S set the LON participant number in coding 1, address 77 (factory default 5).
  6. Allow several minutes for data transfer over the LON system.

Applies to: Multi-boiler systems with LON communication

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitotronic 100 / Vitocontrol-S installation and service instructions, p. 92. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.