Weil-McLain · Boiler troubleshooting
Electrical installation requirements before wiring
What is going on
Basic rules from the manual that must be met before making any electrical connection.
Check in this order
- Turn off the electrical supply at the service entrance panel before making any connection.
- Do not use a 24 V transformer to power any external device that is not listed in the manual.
- Use NEC Class 1 wiring. If the original boiler wire must be replaced, use 105 °C wire or equivalent.
- Electrically ground the boiler as the code requires, and bond it to ground where the authority having jurisdiction requires it.
- Label every wire to make sure connections are correct.
- Do not jumper or bypass any device except for momentary testing.
- Seal all electrical entrances with a sealed strain relief or duct seal putty or silicone so the boiler does not draw room air.
Applies to: All Series 2 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Series 2 advanced manual 550-100-581/0325, p. 45-46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.