Weil-McLain · Boiler troubleshooting
Check heat exchanger, vent seals and condensate dish joint
What is going on
Check for leaks at high fire using an inspection mirror.
Likely causes
- Loose retaining screws or nuts
- Damaged gasket
Check in this order
- Operate the boiler on HIGH fire.
- Move an inspection mirror around all heat exchanger joints, vent pipe connections at the top, and the condensate dish joints.
- A leak shows as vapor on the mirror or signs of weepage.
- If a leak is found, shut the boiler down immediately.
- Tighten retaining screws or nuts without over-tightening.
- If the leak continues, disassemble the joint, inspect gaskets and replace any damaged gasket.
- Contact WM Technologies Technical Services if the problem is not solved.
Applies to: ECO Tec Series 3 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 136. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.