Weil-McLain · Boiler troubleshooting

Check heat exchanger, vent seals and condensate dish joint

ECO Tec Series 3

What is going on

Check for leaks at high fire using an inspection mirror.

Likely causes

  • Loose retaining screws or nuts
  • Damaged gasket

Check in this order

  1. Operate the boiler on HIGH fire.
  2. Move an inspection mirror around all heat exchanger joints, vent pipe connections at the top, and the condensate dish joints.
  3. A leak shows as vapor on the mirror or signs of weepage.
  4. If a leak is found, shut the boiler down immediately.
  5. Tighten retaining screws or nuts without over-tightening.
  6. If the leak continues, disassemble the joint, inspect gaskets and replace any damaged gasket.
  7. Contact WM Technologies Technical Services if the problem is not solved.

Applies to: ECO Tec Series 3 80/110/150/199

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 136. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.