Weil-McLain · Boiler troubleshooting

Clean condensate trap

ECO Tec Series 3

What is going on

Clean the condensate trap at each annual startup.

Likely causes

  • Sediment in trap
  • Blocked condensate drain

Check in this order

  1. Remove the pedestal front access panel if floor standing.
  2. Loosen the hose clamp and pull the trap down to disengage the drain tube.
  3. Remove the clean out cap and take out the trap internal parts.
  4. Clean all trap components.
  5. Reassemble and reinstall all lower gaskets.
  6. Make sure the trap ball moves freely.
  7. Fill the trap with fresh water through the top until water flows out the drain line.
  8. Reattach the trap to the condensate outlet, push up until fully engaged, and retighten the hose clamp.

Applies to: ECO Tec Series 3 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 140. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.