Weil-McLain · Boiler troubleshooting
Check burner flames
What is going on
A proper pilot flame is blue with the inner cone engulfing the pilot flame sensor, and the sensor glows cherry red. A proper main burner flame may show yellow-orange streaks from dust.
Likely causes
- Overfired pilot: large flame lifting or blowing past the sensor
- Underfired pilot: small flame with inner cone not engulfing the sensor
- Lack of primary air: yellow flame tip
- Overfired main burners: large flames
- Underfired main burners: small flames
- Lack of primary air at main burners: yellow tipping and sooting
Check in this order
- Check that the pilot flame is blue, the inner cone engulfs the pilot flame sensor, and the sensor glows cherry red.
- Check that main burner flames are not large, small or yellow-tipped.
- Correct overfired, underfired or primary air problems before continuing.
Applies to: Spark-ignited pilot and main burners in EG / PEG boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 boiler manual, p. 60. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.