Direct vent termination clearances (vent and air through roof)
What is going on
Vent and air terminations through the roof must meet fixed heights and spacings. Air pipe ends in a down-turned 180-degree return bend with its edge at least 12 in above roof or snow line. Vent pipe ends in an up-turned coupling whose top is at least 12 in above the air intake to keep flue products out of the combustion air. Adjacent vent pipes of other boilers need 12 in minimum clearance on US installs. Canadian installs follow CSA B149 and a ULC S636 kit.
Check in this order
- Set the air return bend edge at least 12 in above roof or snow line.
- Set the vent up-turned coupling top at least 12 in above the air intake.
- Keep at least 12 in vertically from vent outlet to any air inlet.
- Keep at least 12 in between adjacent vent pipes of other boilers (US).
- Keep all vent outlets for multiple boilers at the same height.
- Maintain the finished termination dimensions shown in the manual figure.
Applies to: 80/110/150/199 Series 3 direct vent
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Boiler Manual, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.