Viessmann · Boiler troubleshooting
Cleaning the burners
What is going on
Clean the fan and burner tube from the gas valve side, then reassemble and check for gas leaks.
Likely causes
- Dirty fan housing or impeller
- Debris in burner tube
Check in this order
- Close the central gas shut-off valve.
- Disconnect the Venturi mixing tube from the fan.
- Detach the Venturi mixing tube with the combination gas valve and gas connector pipe; detach connector pipes if fitted.
- Detach connector pipes a-Ö and a-ÖA from the fan and remove the fan.
- Clean the fan housing and impeller with compressed air.
- Vacuum the burner tube inside and out if needed.
- Reassemble in reverse order.
- Make sure the gasket between fan housing and burner plate is positioned correctly; replace it if damaged.
- Check screws and the fan-to-burner plate gasket for gas leaks.
Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.