Viessmann · Boiler troubleshooting

Cleaning the burners

Vitocrossal 300 CA3B Dual Fuel

What is going on

Clean the fan and burner tube from the gas valve side, then reassemble and check for gas leaks.

Likely causes

  • Dirty fan housing or impeller
  • Debris in burner tube

Check in this order

  1. Close the central gas shut-off valve.
  2. Disconnect the Venturi mixing tube from the fan.
  3. Detach the Venturi mixing tube with the combination gas valve and gas connector pipe; detach connector pipes if fitted.
  4. Detach connector pipes a-Ö and a-ÖA from the fan and remove the fan.
  5. Clean the fan housing and impeller with compressed air.
  6. Vacuum the burner tube inside and out if needed.
  7. Reassemble in reverse order.
  8. Make sure the gasket between fan housing and burner plate is positioned correctly; replace it if damaged.
  9. Check screws and the fan-to-burner plate gasket for gas leaks.

Applies to: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 72. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.