Connecting the LON gateway to the boiler control
What is going on
Wiring and power connections for the Versatronik gateway on the Vitotronic and Vitodens controls. Refer to the manual for the specific boiler control for the LON card location.
Check in this order
- Install the LON communication card in the boiler control, as described in that control's manual.
- Plug the supplied 3 ft (91 cm) CAT-5 cable into the RJ45 socket in the control and into the RJ45 socket inside the gateway.
- For Vitodens 200 (WB2B, HO1, B2HA), plug the cable into the boiler with the LON card installed; a longer field-supplied cable may be needed depending on distance.
- Wire the LON 2-wire BMS connection to gateway terminals A and B.
- Power the wall-mount 511 (120VAC) with the plug-in power cord.
- Power the DIN-rail 511D (24VAC) from a field-supplied 24VAC supply.
- For Vitocontrol-S, install the LON card before connecting the gateway.
Applies to: Vitotronic 100 GC1/GC1B, Vitotronic 300 GW2/GW5B, Vitotronic 200 HO1, Vitodens 200 B2HA, Vitocontrol-S
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Versatronik 511 and 511D LON Type B manual, pp. 8-13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.