Viessmann · Boiler troubleshooting
Vent termination location requirements - USA
What is going on
Vent must follow local rules plus ANSI Z223.1 or NFPA 54. Flexible vent is only for vertical runs. Key limits: not less than 7 ft (2.13 m) above a paved walk or driveway on public property; 4 ft (1.2 m) horizontally from service regulator vents, electric and gas meters, and relief equipment; 3 ft (0.9 m) above any forced air inlet within 10 ft (3 m); 1 ft (0.3 m) above grade or snow level; 1 ft (0.3 m) from a window, door, or non-mechanical air inlet; 3 ft (0.9 m) from an inside corner of outside walls.
Check in this order
- Confirm the vent does not end inside any listed clearance.
- Keep the termination away from planters, patios, and windows where flue gas causes fogging.
- Keep flue gas away from brick, siding, or other surfaces that can be damaged by heat or condensate.
- Keep the termination 3 ft (0.9 m) from the property line where possible.
Applies to: Vent termination, USA
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Installation Instructions, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.