Viessmann · Boiler troubleshooting

Burner control wiring with plug-in connection, CM2

Vitotronic 300

What is going on

Same plug-in wiring method as the VD2/VD2A/CT3 layout. Burner cables come with the Vitotronic, and the burner side connects to a burner interface.

Check in this order

  1. Disconnect power to the burner and the boiler control.
  2. Connect the 7-pole plug (fA) and the 3-pole plug (lÖ) to the matching counter plugs on the boiler control.
  3. Connect the 7-pole plug (fA) and the 3-pole plug (lÖ) to the burner interface.
  4. Check terminal use 1 from burner, 2 modulating down, 3 modulating up or 2nd stage ON.
  5. Confirm colour codes against the drawing (BK black, BN brown, BU blue).

Applies to: CM2 controls with plug-in burner connection

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 56. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.